Electrical Design according to IEC/ EN61009 Current test marks as printed onto the device Tripping linevoltage-independent instan taneous250A (8/20U) surg ecurrent-proof; Rated voltage Ue 2 30 V; 50Hz Operational voltage range 19 6-253V Rated tripping current In30,10 0,300mA Rated non-tripping current Ino0.5In oSensitivity AC and pulsating DC Selectivity class 3 Rated breaking capacity6/4.5kA Rated current 1-40A Rated peak withstand voltage Uimp 6kV(1.2/50U) Characteristic B/C/D Maximum back-up fuse (short circuit) 100AgL(>4,5kA) Endurance electro-mechanic alcomp ≥4,0 00 operatingcycles Mechanical Frame size 45mm Device height86.4mm Device width 36 mm(2MU) Mounting 3-position DIN railclip, perm itsremov alfrom exist ingbus barsystem Upper and lower terminalsopenmouth ed/liftterminals Terminal protection finge rand handt ouchsafe, Terminal capacity 1-25mm2 Busbar thickness 0.8-2mm Terminal fastening torque2.0Nm Degree of protection switchIP20 Degree of protection,built-in IP40 Tripping temperature- 5 C to+40C Resistance to climatic conditions acc.t oIEC/EN61009